Power supply
Regulations and directives
Danger
Incorrectly executed electrical
installations can result in injuries
from electrical current and dam-
age to the appliance.
Connect the power supply and
implement all safety measures
(e.g. RCD circuit) in accordance
with the following regulations:
■ National regulations:
GB13955-2005
GB50096-2011
GB50575-2010
■ Connection requirements
specified by your local power
supply utility
Power supply to boiler:
■ Protect with a fuse/MCB of up to
16 A.
■ Install residual current device (RCD).
■ Fit a secure earth connection.
■ Install in a securely mounted junction
box.
Routing connecting cables/leads
!
Please note
If connecting cables/leads come
into contact with hot compo-
nents, they will be damaged.
When routing and securing
cables/leads on site, ensure that
the maximum permissible tem-
perature for these is not excee-
ded.
1. Bundle the LV leads on the right
and left and fasten to the hooks.
Installation sequence
Electrical connections
(cont.)