Illustration with the Vitoladens 300-T
A
Secondary ventilation
B
Flue gas
C
Inspection port
D
Connection piece
E
Ventilation air
F
Ventilation air aperture, min. 150 cm
2
or 2 × 75 cm
2
Rated heating output (kW) up to
35.4
from
42.8
System size
Ø mm
1
Boiler flue connection (part of the stand-
ard boiler delivery)
80 100
2
Standard shaft pack (PPs, rigid)
Comprising:
– Support bend
– Support rail
– Shaft cover (PPs)
– Spacers (5 pce, max. clearance 5 m)
or
80 100
Rated heating output (kW) up to
35.4
from
42.8
System size
Ø mm
Standard shaft pack (metal/PPs, rigid)
For twin flue chimneys; one flue for solid
fuel boilers
Comprising:
– Support bend
– Support rail
– Shaft cover (metal)
– Terminal pipe (stainless steel)
– Spacers (5 pce, max. clearance 5 m)
80 100
Spacers (3 pce, max. clearance 5 m) 80 100
3
Pipe 80 100
1.95 m long (2 pce = 3.9 m)
1.95 m long (1 pce)
1 m long (1 pce)
0.5 m long (1 pce)
4
Inspection piece, straight (1 pce) 80 100
5
Bend
87º (1 pce)
45º (2 pce)
80 100
6
Ventilation bezel (1 pce) 80 100
Bend (for use in corbelled chimneys)
30º (2 pce)
15º (2 pce)
80 100
Inspection tee 87º (1 pce) 80 —
Inspection bend 87º (1 pce) — 100
Ventilation air damper 80 100
Stainless steel extension, 380 mm long
for shaft cover, metal/PPs, rigid
80 100
Max. total length of the flue pipe up to the boiler flue connection
when routing through a shaft: 20 m
The following components are taken into consideration for the maxi-
mum flue lengths:
■
Connection pipe D 0.5 m long.
■ 1 bend 87º and 1 support bend 87º
or
■ 2 bends 45º and 1 support bend 87º
Subtract other bends, tees and extension pieces from the maximum
length using the following values:
■ Connection pipe 0.5 m long: 0.5 m
■ Connection pipe 1 m long: 1 m
■ Bend 45º: 0.3 m
■ Bend 87º: 0.5 m
■ Inspection tee: 0.3 m
Design and sizing information for the Vitoladens 300-C, -T, and Vitorondens 200-T, 222-F
(cont.)
16
VIESMANN
VITOLADENS, VITORONDENS
2
5822 452 GB