Viessmann VITORONDENS 200-T - Flue, Flexible, System Size 80 and 100 (Components) (Type B; Plastic (Pps) Flue Pipe for Routing the Flue over External Walls

Viessmann VITORONDENS 200-T
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Flue, flexible, system size 80 and 100 (components) (type B
23
to TRÖI 2009)
2
B
E
C
D
C
2
2
2
2
4
2
5
3
E
9
1
E
A
7
6
8
Illustration with the Vitoladens 300-C
A
Ventilation air aperture, min. 150 cm
2
or 2 × 75 cm
2
B
Flue gas
C
Inspection port
D
Connection piece = ¼ of the vertical length or max. 3 m
E
Secondary ventilation
Note
Install the flexible flue with a maximum offset of 45° from the vertical.
Rated heating output (kW) up to
35.4
from
42.8
System size
Ø mm
1
Boiler flue connection (part of the stand-
ard boiler delivery)
80 100
2
Standard shaft pack (PPs, flexible)
Comprising:
Support bend
Support rail
Shaft cover (PPs)
Spacers (5 pce, max. clearance 2 m)
or
80 100
Standard shaft pack (metal/PPs, flexi-
ble)
For twin flue chimneys; one flue for solid
fuel boilers.
Comprising:
Support bend
Support rail
Shaft cover (metal)
Terminal pipe (stainless steel)
Spacers (5 pce, max. clearance 2 m)
80 100
Spacers (5 pce, max. clearance 2 m) 80 100
3
Flue pipe, flexible, as a 12.5 or 25 m roll 80 100
4
Connection piece for connecting residual
lengths of the flexible flue
80 100
Pipe lowering attachment with 25 m
rope
80 100
5
Inspection piece, straight (1 pce) for
installation into the flexible flue
80 100
6
Inspection piece, straight (1 pce) 80 100
7
Ventilation bezel (1 pce) 80 100
8
Pipe
1 m long (1 pce)
0.5 m long (1 pce)
80 100
9
Bend
87º (1 pce)
45º (2 pce)
or
80 100
Inspection bend 87º (1 pce) 100
Inspection tee 87º (1 pce) 80
Stainless steel extension, 380 mm long
for shaft cover, metal/PPs, flexible
80 100
Max. total flue length: 18 m
The following components are taken into consideration for the maxi-
mum flue lengths:
Connection pipe D 0.5 m long.
1 bend 87º and 1 support bend 87º
or
2 bends 45º and 1 support bend 87º
Subtract other bends, tees and extension pieces from the maximum
length using the following values:
Connection pipe 0.5 m long: 0.5 m
Connection pipe 1 m long: 1 m
Bend 45º: 0.3 m
Bend 87º: 0.5 m
Inspection tee: 0.3 m
2.6 Plastic (PPs) flue pipe for routing the flue over external walls (type B
23
to TRÖI 2009)
The Vitoladens may also be connected, without shaft, to a flue pipe
that is routed over an external wall.
Design and sizing information for the Vitoladens 300-C, -T, and Vitorondens 200-T, 222-F
(cont.)
VITOLADENS, VITORONDENS
VIESMANN
23
5822 452 GB