Viessmann VITORONDENS 200-T - Max. Total Length of the Flue Pipe

Viessmann VITORONDENS 200-T
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Up to 35.4 kW:
Internal flue diameter: Ø 80 mm
Internal diameter, external pipe: Ø 125 mm
From 42.8 kW:
Internal flue diameter: Ø 100 mm
Internal diameter, external pipe: Ø 150 mm
qW
qQ
8
6
7
5
6
4 5
3
1
2
A
qP
7
7
9
2m
C
B
C
C
B
Illustration with the Vitoladens 300-C
A
Ventilation air
B
Flue gas
C
Inspection port
Rated heating output (kW) up to
35.4
from
42.8
System size
Ø mm
1
Boiler flue connection
(Part of the standard boiler delivery)
80 100
2
Pipe
1.95 m long (2 pce of 1.95 m = 3.9 m)
1.95 m long (1 pce)
1 m long (1 pce)
0.5 m long (1 pce)
80 100
3
Inspection piece, straight (1 pce) 80 100
4
Bend
87º (1 pce)
45º (2 pce)
80 100
5
Wall bezel (1 pce) 80/125 100/150
6
Balanced flue pipe
1.95 m long (1 pce)
1 m long (1 pce)
0.5 m long (1 pce)
or
80/125
External wall pipe
1.95 m long (1 pce)
1 m long (1 pce)
0.5 m long (1 pce)
100/150
7
Balanced flue bend
87º (1 pce) 80/125
45º (2 pce)
or
80/125
External wall bend
87º (1 pce) 100/150
45º (2 pce) 100/150
8
Fixing clamp, white (1 pce)
(For balanced flue and pipe for routing over
external walls)
80/125 100/150
9
External wall terminal
For a short roof overhang
80/125 100/150
qP
Universal cover plate 80/125 100/150
qQ
Balanced flue roof outlet outside wall,
with fixing clamp
Colour: black or terracotta
80/125 100/150
Above-roof extensions,
0.5 or 1.0 m long
are available upon request
qW
Universal roof tile
For Roman tiles, pantiles, plain tiles, slate
and other types of roof
Colour: black or terracotta
or
80/125 100/150
Pipe outlet for Klöber roof tiles
Colour: black or terracotta
(provide the corresponding Klöber tile on
site to match the roof outlet selected for the
particular type of roof)
80/125
Max. total length of the flue pipe
Rated heating output
at system temperature 50/30 °C
kW 19.3 20.2 23.5 24.6 28.9 35.4 42.8 53.7 67.6 85.8 107.3
Max. length for system size Ø 80 mm m 15 15 18 18 18 22
Max. length for system size Ø 100 mm m 22 22 22 22 22
The following components are taken into consideration for the maxi-
mum flue lengths:
Connection pipe D 0.5 m long.
2 bends 87º
or
3 bends 45º
Subtract other bends, tees and extension pieces from the maximum
length using the following values:
Connection pipe 0.5 m long: 0.5 m
Connection pipe 1 m long: 1 m
Bend 45º: 0.3 m
Bend 87º: 0.5 m
Inspection tee: 0.3 m
Design and sizing information for the Vitoladens 300-C, -T, and Vitorondens 200-T, 222-F
(cont.)
24
VIESMANN
VITOLADENS, VITORONDENS
2
5822 452 GB