EasyManua.ls Logo

VIPA System 300V - Page 89

Default Icon
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual VIPA System 300V Chapter 5 Deployment CPU 31x with Profibus
HB130E - CPU - Rev. 11/50 5-9
Note!
To connect this plug, please use the standard Profibus cable type A
(EN50170). Starting with release 5 you also can use highly flexible bus
cable: Lapp Kabel order no.: 2170222, 2170822, 2170322.
Under the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating
tool, that makes the connection of the EasyConn much easier.
11 6
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to
activate a terminating resistor.
Attention!
The terminating resistor is only effective, if the connector
is installed at a slave and the slave is connected to a
power supply.
Note!
A complete description of installation and deployment of
the terminating resistors is delivered with the connector.
Loosen the screw.
Lift contact-cover.
Insert both wires into the ducts provided
(watch for the correct line color as below!)
Please take care not to cause a short
circuit between screen and data lines!
Close the contact cover.
Tighten screw
(max. tightening torque 4Nm).
The green line must be connected to A, the red line to B!
Termination with
"EasyConn"
Assembly