33
EDITION 08/2021
ORDER NUMBER DOC241936
IP 5000
7.5 SETTING ELEMENTS IN THE CONTROL CABINET
7.5.1 DIP SWITCH FUNCTIONS
Function No. Switch No. 1 2 3 4 5 6 7 8 Explanation
1
on 1 on = use of powder center*
o (hose lengths < 20 m)
1
on 1 o = use of BigBag*
o (hose lengths > 20 m)
2
on
2 on = recipe "soft"
o
2
on
2 o = recipe "normal"
o
3
on
3+4 o = set after-run time
o
4
on 3 on
o 4 o = set cleaning time
5
on 5 on = internal cleaning
o (without cleaning box)
5
on 5 o = external cleaning
o (with cleaning box)
6
on 3 o
o 4 on = set service interval
7
on
3+4 on = set level controller time
o
8
on 6 on = standby deactivated
o (from software version 1.03)
9
on
SuperCenter Cleaning Procedure
o
10
on
PXM Cleaning Procedure
o
11
on
For service purposes only, must be set to
"o"
o
The terms powder center or BigBag are synonymous for the distance of the pump to
the target tank.
Powder center distance < 20 m; 66 ft
BigBag distance > 20 m; 66 ft
7.5.2 A+/A BUTTONS
With functions 2, 3, 4, 6, 7 and 9, the parameters can be adjusted with the A+/A- buttons
(see Chapter 6.9.3).
Note:
Only the parameters of the function currently set with the DIP switches can be changed.