6.2 Industrial Bluebirds
2.5
10
145
Danfoss 60°S
MODEL
Output Range kW
Nominal Heat kW
Input Btu
Nominal Heat kW
Output Btu
Burner
Head
Flue Size mm
Dia in
NFGT (max output) °C
CO
2
Smoke Bacarach
Nozzle make
(Kerosine) size
Pump bar
Pressure psi
Nozzle make
(Gas Oil) size
Pump bar
Pressure psi
Approx Fuel L/h
Flow Rate gals/h
Water Connections x 4
Water litres
Content gallons
Max Water mbar
resistance at 20°C T
Max Water mbar
resistance at 10°C T
Weight (empty) kg
Weight (full) kg
300
88.0
97.7
333,333
88.0
300,000
G10
3.5
203
7 or 8
195
11.0
0 1
Danfoss 60°S
2.0
12
175
10.2
2.25
3 BSP
188
41.4
3.1
21.0
782
970
400
117.2
130.2
444,444
117.2
400,000
G20S
2
203
7 or 8
190
11.0
0 1
2.5
12
175
13.6
3.0
3 BSP
272
59.8
3.1
21.0
1,045
131
500
146.6
162.8
555,555
146.6
500,000
G20S
3.5
203
7 or 8
190
11.0
0 1
3.5
12
175
17.0
3.75
3 BSP
411
90.5
3.1
21.0
1,431
1,842