3 Product description
83299902 1/2019-02 La
18-124
3.4.5 Emissions
Flue gas
To EN676 the burner complies with emission class 3.
The NOx values are influenced by:
combustion chamber dimensions
flue gas system
combustion air (temperature and humidity)
medium temperature
Sound levels
Dual number noise emission values
Measured sound power level LWA (re 1 pW)
Uncertainty value KWA
79
4
dB(A)
(1
dB(A)
Measured sound pressure level LpA (re 20 μPa)
Uncertainty value KpA
75
4
dB(A)
(2
dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which
could occur when measuring.