12.Electricalconnection
Generalinformation
Theinstallationmaybecarriedoutonlyby
anapprovedelectricalcontractor.Observe
VDE regulations[Germany] and all local
regulationsofyourpowersupplyutility.
For installation inAustria: The ÖVE reg-
ulationsand requirements and those of
your local power supply utility must be
observed.
Anomnipolarisolatorwithatleast3mm
contactseparationmustbeintegratedin
thepowercableupstreamoftheappliance.
A connectionbox mustalso beinstalled
onsite.
Neverroutesensorleadsalongside230V
cables.
Danger through 'live' electrical compo-
nents.
Pleasenote: Turnoff theON/OFF switch
beforeremovingthecasing.
Nevertouchelectricalcomponentsorcon-
tactswhentheON/OFFswitchisintheON
position.Thereisadangerofelectrocution,
resultinginarisktohealthordeath.
The main terminals are 'live', even when
theON/OFFswitchisintheOFFposition.
Duringservicing and installation work,
isolatetheentiresystemfromthepower
supply across all poles, otherwise there
willbeariskofelectrocution.