Sensorresistances
Resistance [Ohm]
Temperature [°C]
Temperature/resistance
0°C 16325 15°C 7857 30°C 4028 60°C 1244
5°C 12697 20°C 6247 40°C 2662 70°C 876
10°C 9952 25°C 5000 50°C 1800 80 °C 628
Max.spread
A heat exchanger protective functionisintegratedintotheCGB-75/100. This prevents
stressesinthematerialbylimitingthemaximumtemperaturedifferentialbetweenow
and return. The output is restricted at 28 K and above. If 38 K is nevertheless reached, the
burnershutsdownbrieywithoutafaultmessage.Thischaracteristicmustbetakeninto
account when selecting the components (e.g. pumps, heat exchangers and cylinders).
Max.owrate
Excessiveowvelocitiesmayleadtoerosion.
MaximumowrateatQ
max
: CGB-75/100 6000 l/h (100 l/min)
1)
Mark"x"indicatesthatallcomponentsoftheuearesur-
rounded by combustion air and meet higher requirements
for gas tightness.
2)
For type B23, B33 the combustion air is drawn from the
installationroom(openuegascombustionequipment).
3)
In Switzerland, observe the G1 gas guidelines!
For type C, combustion air is drawn through a sealed system
from the outside (room sealed combustion equipment).
Connectiontypes
Device Type
1)
Operating mode Can be connected to
Openue Balanced
ue
chimney
moisture resistant
Balanced
ue
chimney
Air/uegas
routing
Certied
balanced
ue
Moisture
resistantue
CGB-
75/100
B23, B33, C13x
3)
,
C33x, C43x, C53,
C53x, C63, C83x,
C93x
X X B33, C53, C83x C43x C13x
2)
,
C33x, C53x
C63x B23, C53x,
C83x, C93x
Category: Germany II
2ELL3P,
Austria II
2H3P,
Switzerland I
2H