42 3062555_201804
25.Maintenanceanddesigndata
Sensorresistances
Resistance [Ohm]
Temperature [°C]
Temperature/resistance
0°C 16325 15°C 7857 30°C 4028 60°C 1244
5°C 12697 20°C 6247 40°C 2662 70°C 876
10°C 9952 25°C 5000 50°C 1800 80 °C 628
Max.spread
A heat exchanger protective functionisintegratedintotheCGB-75/100. This prevents
stressesinthematerialbylimitingthemaximumtemperaturedifferentialbetweenow
and return. The output is restricted at 28 K and above. If 38 K is nevertheless reached, the
burnershutsdownbrieywithoutafaultmessage.Thischaracteristicmustbetakeninto
account when selecting the components (e.g. pumps, heat exchangers and cylinders).
Max.owrate
Excessiveowvelocitiesmayleadtoerosion.
MaximumowrateatQ
max
: CGB-75/100 6000 l/h (100 l/min)
1)
Mark"x"indicatesthatallcomponentsoftheuearesur-
rounded by combustion air and meet higher requirements
for gas tightness.
2)
For type B23, B33 the combustion air is drawn from the
installationroom(openuegascombustionequipment).
3)
In Switzerland, observe the G1 gas guidelines!
For type C, combustion air is drawn through a sealed system
from the outside (room sealed combustion equipment).
Connectiontypes
Device Type
1)
Operating mode Can be connected to
Openue Balanced
ue
chimney
moisture resistant
Balanced
ue
chimney
Air/uegas
routing
Certied
balanced
ue
Moisture
resistantue
CGB-
75/100
B23, B33, C13x
3)
,
C33x, C43x, C53,
C53x, C63, C83x,
C93x
X X B33, C53, C83x C43x C13x
2)
,
C33x, C53x
C63x B23, C53x,
C83x, C93x
Category: Germany II
2ELL3P,
Austria II
2H3P,
Switzerland I
2H