AccordingtoTRGI:
Connection to a moisture-resistant balanced ue
chimney(LAS),uegaschimneyoruesystem
Chimneysanduesystemsmustbecertiedforcombustion
equipment in accordance with local Building Regulations (CE
/DIBTcertication).Dimensioningiscarriedoutusingthecal-
culationtablesaccordingtotheuegascategory.Inaddition
to the boiler connection bend or tee piece, up to two 87°/90°
diversions may be installed. Approval is required for positive
pressure operation.
Connection to a moisture-resistant balanced ue
chimneytypeC43x
Straightbalanceduesmaybeupto2.0mlong,wheninstall-
ingthesysteminabalanceduechimney. In addition to the
boiler connection bend, up to two 87° bends may be installed.
Thebalanceduechimneymustbecertied[inGermany]by
the DIBT - Deutsches Institut für Bautechnik and must also
be approved for condensing operation with positive pressure.
Connectiontomoisture-resistantuegaschimney
orauegassystemtype,B33foropenueoperation
Straight balanced ues must be no longer than 2 m when
connectingthesystemtoauegaschimney. In addition to the
boiler connection bend, up to two 87° bends may be installed.
TheuegaschimneymustbecertiedbyDIBT[Germany]
and must be approved for condensing operation.
If necessary, obtain the connection piece from the chimney
manufacturer.
The air apertures to the boiler room must be completely free
from obstruction.
Connectiontomoisture-resistantue,typeB23for
openueoperation
Thestraight,horizontaluemustnotbelongerthan3m.
In addition to the boiler connection bend, up to two 87° diver-
sionsmaybeinstalledintothehorizontalue.
For this option, observe the regulations concerning ventilation
for boiler rooms acc. to DVGW-TRGI.
Connectionto moisture-resistant ue, type C53,
C83x,forroomsealedoperation
Thestraight,horizontaluemustnotbelongerthan3m.For
horizontal air supply pipes, a maximum length of 3 m is recom-
mended.Observethespecialrequirementsforuesthatare
not surrounded by combustion air acc. to DVGW-TRGI 2008
and all locally applicable combustion regulations.
Connectionto a combustion air and uesystem
typeC63xthatisnottestedtogetherwiththegas
combustionequipment
Original Wolf components are designed for long term use,
are designated with the DVGW quality seal and are designed
for use with Wolf gas condensing boilers. If using third party
equipment that is only DIBT or CE certied, the installer is
responsible for the correct sizing and correct function of the
system. Faults, material losses and injuries resulting from in-
correct pipe lengths, excessive pressure drop, premature wear
withescapinguegasandcondensateorincorrectfunction,
e.g. through components working themselves loose, are ex-
cluded from our warranty if third party equipment that is only
DIBT/CEcertiedisused.Straightbalanceduesmustbeno
longer than 2 m, when connecting the system to a combustion
air supplyandaseparateue.
In addition to the boiler connection bend, up to two 87°/90°
bends may be installed.
If the combustion air is drawn from the duct, the duct must be
free from contamination.