Example Configurations
Example 1
Settings:
• f controller: output range 0 to 20mA (0 to 10V)
• Jumper between terminals 8 and 9 yes
• Initial state frequency 50%
• f controller: minimum value 20%
• f controller: maximum value 60%
Controller output:
• f controller: minimum value 20% from 0 to 10V = 2V
• f controller: maximum value 60% from 0 to 10V = 6V
• Initial state frequency 50% from 2V to 6V = 4V
Controller range
(0%) (50%) (100%)
V 2 4 6
|.........|.........|.........|.........|.........|.........|.........|.........|.........|.........|
0 5 10
(0%) (50%) (100%)
Total range
Example 2
Settings:
• f controller: output range +/- 20mA (+/- 10V)
• Jumper between terminals 8 and 9 no
• Initial state frequency 25%
• f controller: minimum value 40%
• f controller: maximum value 80%
Controller output:
• f controller: minimum value 40% from - 20mA to + 20mA = - 4mA
• f controller: maximum value 80% from - 20mA to + 20mA = +12mA
• Initial state frequency 25% from - 4mA to + 12mA = 0mA
Controller range
(0%) (25%) (100%)
mA -4 0 12
|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|...|
-20 0 20
(0%) (50%) (100%)
Total range