Manual 37240C GCP-30 Series - Genset Control
Analog Controller Output Value in Initial Position
≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
NOTE
This functionality is only valid for GCP-30 Packages which are equipped with analog controllers.
The analog value, which is output from the GCP-30 in initial controller position depends on the setting of various
parameters. The following examples show this behavior.
Parameters
F/P contr.output
----------------
f controller: output range refer to parameter description for settings
If the parameter "F/P contr.type" has been configured to "ANALOG", this parame-
ter must be configured to the appropriate type of analog controller. The range of the
analog output is configured here. To switch from a current to a voltage or PWM
output a jumper must be added to terminals 8/9.
Initial state
Frequency 000%
f controller: initial frequency 0 to 100 %
Analog controller output setting with disabled controller. The set value in percent
refers to the range between minimum and maximum value of the output signal.
Stepper sign.frq
(min.) 000%
f controller: minimum value 0 to 100%
This parameter permits the operator to clamp or limit the lower analog output
value.
Stepper sign.frq
(max.) 000%
f controller: maximum value 0 to 100%
This parameter permits the operator to clamp or limit the upper analog output
value.
Page 32/38 © Woodward