Woodward EGCP-2 - User Manual

Woodward EGCP-2
234 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Product Manual 26174
(Revision B)
Original Instructions
EGCP-2
Engine Generator Control Package
8406-120, 150–300 Vac PT Input, 9–32 Vdc
8406-121, 50–150 Vac PT Input, 9–32 Vdc
Installation and Operation Manual

Table of Contents

Other manuals for Woodward EGCP-2

Questions and Answers

  • L
    lucas09Sep 9, 2025
    What should I do if phase power factors do not agree on my Woodward EGCP-2 Controller?
    • M
      Mary Hughes DVMSep 10, 2025
      If phase power factors do not agree and two of the three phases are extremely far out of range, the CT’s are likely connected to incorrect phase inputs. Verify that the CT’s are connected to the appropriate input terminals. Note: The engine generator set must be off to safely open circuit a current transformer.
  • S
    sarahhammondAug 25, 2025
    How to troubleshoot unstable engine speed/load with Woodward Controller?
    • E
      Emily EdwardsAug 25, 2025
      If the engine speed/load has an instability that fluctuates very quickly, it's likely that the speed control dynamics are improperly set up. You'll need to tune the speed control dynamics for stable operation. Consult the speed control manufacturer’s instruction manual for detailed instructions.
  • E
    Elizabeth JordanAug 25, 2025
    What to do if my Woodward EGCP-2 Controller unit does not power up?
    • G
      Gary GuzmanAug 26, 2025
      If your Woodward Controller unit isn't powering up, there are a couple of things to check: * First, make sure the input power supply is connected correctly to terminals 1 and 2, and that it's providing between 9 and 32 Vdc. * Second, verify that the polarity of the power supply is correct.
  • B
    Brian BellSep 23, 2025
    What to do if I/O STATUS shows relay is energized but alarm does not occur on Woodward Control Unit?
    • E
      Eric SilvaSep 23, 2025
      If the I/O STATUS screen on your Woodward Control Unit shows a relay is energized, but the corresponding action (like an alarm) does not occur, the problem is likely due to faulty wiring of the relay output contacts. Verify the wiring of the relay output contacts to ensure they are correctly connected.
  • W
    walshtylerSep 12, 2025
    How do I fix a Woodward EGCP-2 that carries an improper proportion of reactive load during isochronous load sharing?
    • A
      Ashley WilsonSep 12, 2025
      If the unit carries an improper proportion of reactive load during isochronous load sharing: * The Rated KVA set point in the configuration menu may be set at an incorrect value. Appropriately set the Rated KVA set point in the configuration menu. * The Generator A phase PT input(s) may be improperly calibrated. Calibrate the Generator A phase PT input(s) of the generator set(s).
  • E
    ericksonjenniferSep 15, 2025
    Why does my Woodward EGCP-2 sequence off more than one set when the system load is small enough?
    • S
      samanthadrakeSep 15, 2025
      If more than one set is sequenced off line when the system load is small enough to take additional sets off line, it may be because: * The REDUCED LOAD DELAY set point in the sequencing menu is too short. Increase the REDUCED LOAD DELAY set point in the sequencing menu. * The MAX STOP TIME set point in the sequencing menu is too short. Increase the MAX STOP TIME set point in the sequencing menu.
  • R
    Renee MartinSep 4, 2025
    Why does my Woodward EGCP-2 synchronizer match phase but never closes the breaker?
    • R
      Rachael SimonSep 4, 2025
      If the synchronizer matches phase but never closes the breaker/contactor, it could be due to: * The Synchronizer Mode set point in the synchroscope menu being set to CHECK. Set the Synchronizer Mode to the appropriate setting. * The Dwell Time set point in the synchroscope menu being too large. Reduce the Dwell Time set point in the synchroscope menu.
  • E
    Erin AguirreSep 5, 2025
    What to do if the Woodward EGCP-2 synchronizer does not voltage match within spec?
    • J
      Jack KlineSep 5, 2025
      If the synchronizer does not voltage match within specification, consider the following: * The Generator A phase PT and/or Bus A phase PT input(s) may be inadequately calibrated. Calibrate the Generator A phase PT and Bus A phase PT inputs. * The Voltage matching tolerance set point in the synchroscope menu may be too large. Appropriately set the Voltage matching tolerance set point in the synchroscope menu.
  • M
    millerpeterSep 23, 2025
    Why generator voltage fluctuates on Woodward Control Unit?
    • R
      Renee ChapmanSep 23, 2025
      If the generator voltage fluctuates or is unstable at no load on the generator with your Woodward Control Unit, the AVR dynamics might be improperly set up. You should tune the AVR dynamics for stable operation.
  • R
    Randy JenkinsAug 30, 2025
    How do I resolve unstable real load control in Woodward Controller when paralleled with the mains source?
    • R
      rogerscraigAug 30, 2025
      If the real load control is unstable when paralleled with the mains source, the real load control dynamics in the real load control menu are likely improperly set up. Tune the real load control dynamics in the real load control menu.

Summary

Warnings and Notices

Personal Protective Equipment

Details essential PPE for handling equipment, including eye protection, hard hat, gloves, safety boots, and respirator.

Start-up Precautions

Advises preparedness for emergency shutdown during engine or prime mover startup to prevent runaway or overspeed.

Electrostatic Discharge Awareness

Electrostatic Precautions

Outlines procedures for handling static-sensitive electronic parts to prevent damage, including grounding and material avoidance.

Chapter 2. Control Overview

Chapter 3. Electrical Installation and Specifications

Grounding for Protection Against Electric Shock

Details protective earth connection requirements and recommended single-point grounding practices.

Alarms and Shutdowns

Explains configurable alarm/shutdown set points and their responses (Disabled, Warning, Visual, Audible, Soft/Hard Shutdown).

Chapter 4. Software Overview

Shutdowns and Alarms

Covers configuring generator protection functions, including voltage and frequency limits and alarms.

Chapter 5. Control Features and Functions

Generator Voltage and Reactive Load Control

Explains control of generator voltage for synchronization, load sharing, and reactive load management.

Mains Sensing

Covers sensing mains voltage, frequency, load surge, and loss of mains conditions.

Synchronizing

Details synchronization modes (Run, Check, Permissive), voltage matching, and dead bus closing.

Load Control

Describes load control functions: proportional load sharing, base load, process control, and load ramping.

Sequencing

Explains how units are sequenced on/off line based on system load, priority, and time delays.

Loss Of Mains Detection and Action

Details the EGCP-2's response to loss of mains, including isolation and transfer to on-site generators.

Generator Sequencing

Explains automatic sequencing for multiple units to maintain load capacity ratio and system stability.

Chapter 6. Calibration of Control Inputs and Outputs

Calibration of Generator PTs and CTs

Covers calibration of three-phase generator voltage and current inputs for accurate readings.

Calibration of the Bus PT

Details calibrating bus and mains PT inputs for voltage sensing during monitoring and synchronization.

Speed Bias Output

Explains setting the speed bias offset for governing speed in synchronization and load control functions.

Voltage Bias Output

Describes setting the voltage bias offset to impose an offset voltage on the AVR's bias input.

Chapter 7. General Start-up Instructions

Before Starting the Generator Set

Covers pre-start configuration of tuning set points, verifying wiring, and checking power supply.

Sequence of Start-up and Checking Parameters

Lists sequential steps for system setup, discrete input checks, and parameter verification before loading.

Loading the Generator Set

Provides instructions for loading the generator set, including mains parallel setup and phasing checks.

Chapter 8. Troubleshooting

Control Hardware and I;O

Guides users through troubleshooting issues related to control power, I/O status, and relay outputs.

Engine Control;Sensing Parameters

Addresses problems with starting, starter engagement, engine speed instability, and power loss during cranking.

Synchronization

Helps diagnose and resolve issues with phase matching, breaker closure, voltage matching, and dead bus closing.

Real Load Control

Troubleshoots problems with negative kW readings, improper load sharing, and unstable load control.

Reactive Load Control

Addresses phase power factor disagreements, improper reactive load sharing, and unstable VAR/PF control.

Sequencing

Helps resolve issues where units do not show in sequencing order or auto-sequencing fails.

Woodward EGCP-2 Specifications

General IconGeneral
Display TypeLCD
Isochronous Load SharingYes
kW Load ControlYes
kVAR Load ControlYes
Power Factor ControlYes
Output Voltage24 VDC
Communication ProtocolsJ1939
Operating Temperature-40°C to +70°C
ApplicationsGenerator control
Operating ModesIsochronous, Droop, Base Load
ProgrammingConfigurable via software