Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 105
Process Input Scale
Measure the actual Process Input Signal from external transducer.
Calibrate the Process Input Scale until the Process Input, bottom line on
display screen, reads what the measured process signal is.
Figure 4-33. Process In Scale
Measured vs Monitored
A
B
C
ALARMS: 1 UNIT: 1
Mains: -- Gen: ++
Engine: RUNNING
AUTO: ISOCHRONOUS
A PHASE PT SCALE
1.00
-----------------------------------------------------------------------
PHASE A VL-L: 482.5
Woodward
ALARM / EVENT
ALARM CLEAR
SCRO
LL
ESC
ENTER
SYSTEM
ENGINE
GE
N
I/
O
SYN
C
KW LOAD
PF /
KVAR
SEQUENCE ATS
i
STATUS CONFIG
.
.
.
EGCP-2
Digital Control
480.0
vac
Measured vs. Monitored
Monitored Voltage
EGCP-2 configured for Line to Line (3 wire) PT input.
Calibrate the
Monitored
Value to equal the
Measured
value using Calibration menu items.
480.0 VAC Measured A -B
phase Line to Line
VIS-141
00-6-20
Figure 4-34. Measured vs. Monitored