EGCP-2 Engine Generator Control Package Manual 26174
214 Woodward
Synchronizer Menu
Item: Range: Default:
A
s Set Value: Note:
SYNC MODE Check
Permissive
Run
Check
SYNC GAIN Min: 0.01
Max: 100.00
0.10
SYNC STABILITY Min: 0.00
Max: 20.00
1.00
VOLTAGE
MATCHING
Disabled
Enabled
Enabled
VOLTAGE
WINDOW
Min: 0.1
Max: 10.0
1.0%
MAX PHASE
WINDOW
Min: 2.0
Max: 20.0
10.0°
DWELL TIME Min: 0.1
Max: 30.0
0.5 s
CB HOLD TIME Min: 0.1
Max: 30.0
1.0 s
CLOSE
ATTEMPTS
Min: 1
Max: 20
2
RECLOSE DELAY Min: 2
Max: 1200
30 s
SYNC RECLOSE
ALM
Warning
Visual Alarm
Audible Alarm
Warning
SYNC TIMEOUT Min: 0
Max: 1200
0 s 0 = NO LIMIT
SYNC TIMEOUT
ALM
Warning
Visual Alarm
Audible Alarm
Warning
DEADBUS
CLOSURE
Disabled
Enabled
Disabled