Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 85
0
Power
Level
Time
Reverse Powe
Level
Trip
Instant
Trip
Minimum
Reverse Powe
-5%
-10%
+
Figure 4-25. Reverse Power
Figure 4-25 shows Reverse Power. The first time the power level decreases
below the Minimum Reverse Power setting does not last long enough to cause a
trip. The second time the accumulating amount reaches the calculated delay and
a trip is received. Dropping below Reverse Power Level would cause a trip
instantly.
Reverse KVAR Limit
Range: –.0 to –00
Set as a percentage of the Rated kVAR. If the EGCP-2 senses a kVAR load
greater than this value the Reverse kVAR Delay begins. When the Delay
times out, an alarm will trigger.
Used to indicate loss of field excitation to the generator.
Reverse KVAR Delay
Range: 0.1 to 5.0 seconds.
Provides a delay before triggering the Alarm.
Remote Faults #1 through #6
Each fault is programmable for:
disabled
warning
visual alarm
audible alarm
soft shutdown
hard shutdown
Remote Faults #1 through #6:
Each alarm has a programmable time delay (0 to 30 seconds).
Each alarm can be set for any of the standard alarm or shutdown levels.
Remote Faults 1 and 2 can have a Stable Delay time Enabled or Disabled.
When Enabled a 15 second timer will begin after the Gen Stable period has
expired.