What should I do if phase power factors do not agree on my Woodward EGCP-2 Controller?
- MMary Hughes DVMSep 10, 2025
If phase power factors do not agree and two of the three phases are extremely far out of range, the CT’s are likely connected to incorrect phase inputs. Verify that the CT’s are connected to the appropriate input terminals. Note: The engine generator set must be off to safely open circuit a current transformer.