EGCP-2 Engine Generator Control Package Manual 26086
136 Woodward
Sequencing and Comms Menu
Item: Range: Default: As Set Value: Note:
AUTO
SEQUENCING
Disabled
Enabled
Disabled
MAX GEN LOAD Min: 1
Max: 100
60 %
NEXT GENSET
DLY
Min: 1
Max: 1200
30 sec
RATED LOAD
DELAY
Min: 1
Max: 1200
5 sec
MAX START
TIME
Min: 1
Max: 1200
30 sec
MIN GEN LOAD Min: 1
Max: 100
30 %
REDUCED LOAD
DLY
Min: 1
Max: 1200
60 sec
MAX STOP TIME Min: 1
Max: 1200
60 sec
422 PROTOCOL ServLink
Modbus®
Upload Setpoints
Modbus
Modbus ID Min: 1
Max: 247
1
Modbus Timeout Min: 0.1
Max: 20.0
3.0 sec
Modbus Reset False
True
False