EGCP-2 Engine Generator Control Package Manual 26086
62 Woodward
Synchronizer
Calibrates phase angle error detection of EGCP-2.
Factory calibrated for zero phase angle error between bus and mains A
phase (depending on synchronizing operation) and A phase generator
inputs.
With synchronizer in “check” mode, and a live bus, monitor the
synchroscope menu of the EGCP-2 for “phase angle”.
Monitor Voltage across open gen contactor/breaker or panel synchroscope
for phase angle error between generator and bus.
Adjust synchroscope calibration for lowest voltage across gen breaker, or
12 o’clock reading on panel mounted synchroscope.
Freq.
Analog Input
(Hz)
Figure 3-36. Direct proportional input to Water Temp or Oil Pressure Input.
Freq.
Analog Input
Increasing offset
Decreasing offset
Figure 3-37. Voltage Controlled Oscillators—Effect of Offset
Increasing gain
Decreasing gain
Figure 3-38. Voltage Controlled Oscillators—Effect of Gain