EGCP-2 Engine Generator Control Package Manual 26086
34 Woodward
Rated KW (numeric)
Rated KW of Generator.
Rated KVA (numeric)
Used to determine Rated Current (I) of Generator for minimum overcurrent
level.
Equation used to determine Rated Current:
Voltage input is DELTA I = KVA x 1000
Voltage Ref x 1.73
Voltage input is WYE I = KVA x 1000
Voltage Ref x 3
Rated KVAR (numeric)
Rated KVAR of Unit.
Typically 0.6 x Rated KVA.
KVA
KW
KVAR
KW/KVA=PF
COS =KW/KVA
KVA^2=KW^2+KVAR^2
KVA= (KW^2 + KVAR^2)
Figure 3-17. AC Power Triangle
CT Ratio (numeric :5)
Scales sensed CT input for Amperage as seen at generator.
Used for Load Sensing Algorithm.
(KVA, KW, KVAR, PF)
Used for Alarms/Shutdowns.
Over Current, KW Limits, Reverse Current, etc.
PT Ratio (numeric : 1)
Scales sensed PT input to Voltage Levels as measured at the Generator.
Used in Load Sensing Algorithm.
(KVA, KW, KVAR, PF)
Used for Voltage Matching.
Used for Generator Frequency Detection.
Used for Alarm/Shutdown sensing.
Over/Under Voltage
KW Limits, etc.