Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 35
Voltage Input (Wye L-N, Delta L-L)
Set for sensing/transformer used between generator and EGCP-2.
Defines which calculations will be used for KW, KVA, KVAR, etc.
Defines the expected input type for voltage levels in the setpoint menus.
Sets the label used for all generator and mains voltage Status readings.
Wye (Star) Generator or Transformer Connection
4 Wire
Volts Line to Neutral expected for all setpoint menu items requiring voltage
settings.
Delta Generator or Transformer Connection
3 Wire
Volts Line to Line expected for all setpoint menu items requiring voltage
settings.
Voltage Reference (numeric)
Operating Voltage of Generator per Generator Nameplate.
Used for VAR/PF Sharing as the Reference that multiple generators share
reactive load to. This maintains the voltage reference while in Power Factor
Sharing or KVAR Control mode on an isolated bus.
Display Units
Metric
Sets temperature readings to degrees Celsius (C) , and pressure to Bar
(BAR).
US
Sets temperature readings to degrees Fahrenheit (F), and pressure to
Pounds per Square Inch (PSI).
Set Date
Sets the date used by the control for Alarm / Event time stamps, and
displays.
Set Time
Sets the time used by the control for Alarm / Event time stamps, and
displays.
Start Sequencing
ENABLED or DISABLED to select Start Sequencing Process
Enabled
Uses Preglow time and Engine Crank.
Must have MPU to function.
Disabled
No Preglow Time or Engine Crank
Will operate without an MPU
Relay #12 Function
KVA Load Switch
Defines Discrete Output #12 as a KVA load switch.
Uses KVA High and KVA Low value items in the Load Control Configuration
Menu.