Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 59
Measured vs Monitored
A
B
C
ALARMS: 1 UNIT: 1
Mains: -- Gen: ++
Engine: RUNNING
AUTO: ISOCHRONOUS
A PHASE PT SCALE
1.00
-----------------------------------------------------------------------
PHASE A VL-L: 482.5
Woodward
ALARM / EVENT
ALARM CLEAR
SCRO
LL
ESC
ENTER
SYSTEM
ENGINE
GE
N
I/
O
SYN
C
KW LOAD
PF /
KVAR
SEQUENCE ATS
i
STATUS CONFIG
.
.
.
EGCP-2
Digital Control
480.0
vac
Measured vs. Monitored
Monitored Voltage
EGCP-2 configured for Line to Line (3 wire) PT input.
Calibrate the
Monitored
Value to equal the
Measured
value using Calibration menu items.
480.0 VAC Measured A -B
phase Line to Line
VIS-141
00-6-20
Figure 3-32. Measured vs. Monitored
Speed Bias Offset
Factory calibrated for 0 Vdc offset on ±3 Vdc range.
All Woodward Speed controls operate with this bias output, so no calibration
should be required.
Calibration may be required for other manufacturer’s speed controls.
Voltage Bias Offset
Factory set for zero Volts DC.
Configuration selectable ±1 Vdc, ±3 Vdc, ±9 Vdc range.
Some regulators require a positive voltage bias offset because they cannot
receive a negative voltage bias command. Any bias offset calibrated into the
voltage bias will be displayed in the I/O status menu.
The EGCP-2control will always reset to the voltage bias offset when off line.