Manual 26086 EGCP-2 Engine Generator Control Package
Woodward 59
Measured vs Monitored
A
B
C
ALARMS: 1 UNIT: 1
Mains: -- Gen: ++
Engine: RUNNING
AUTO: ISOCHRONOUS
A PHASE PT SCALE
1.00
-----------------------------------------------------------------------
PHASE A VL-L: 482.5
Woodward
ALARM / EVENT
ALARM CLEAR
SCRO
LL
ESC
ENTER
SYSTEM
ENGINE
GE
N
I/
O
SYN
C
KW LOAD
PF /
KVAR
SEQUENCE ATS
i
STATUS CONFIG
.
.
.
EGCP-2
Digital Control
480.0
vac
Measured vs. Monitored
Monitored Voltage
EGCP-2 configured for Line to Line (3 wire) PT input.
Calibrate the
Monitored
Value to equal the
Measured
value using Calibration menu items.
480.0 VAC Measured A -B
phase Line to Line
VIS-141
00-6-20
Figure 3-32. Measured vs. Monitored
Speed Bias Offset
• Factory calibrated for 0 Vdc offset on ±3 Vdc range.
• All Woodward Speed controls operate with this bias output, so no calibration
should be required.
• Calibration may be required for other manufacturer’s speed controls.
Voltage Bias Offset
• Factory set for zero Volts DC.
• Configuration selectable ±1 Vdc, ±3 Vdc, ±9 Vdc range.
• Some regulators require a positive voltage bias offset because they cannot
receive a negative voltage bias command. Any bias offset calibrated into the
voltage bias will be displayed in the I/O status menu.
• The EGCP-2control will always reset to the voltage bias offset when off line.