EGCP-2 Engine Generator Control Package Manual 26086
128 Woodward
Shutdown and Alarms Menu
Item: Range: Default: As Set Value: Note:
VOLTAGE RNG
ALM
Audible Alarm
Visual Alarm
Warning
Disabled
Warning
GEN VOLT HI
LMT
Min: 50
Max: 30000
250.0 volts
GEN VOLT HI
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
GEN VOLT LO
LMT
Min: 50
Max: 30000
200.0 volts
GEN VOLT LO
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
VOLTAGE ALM
DLY
Min: 0.1
Max: 30.0
5.0 sec.
GEN FREQ HI
LMT
Min: 40
Max: 75
65 Hz
GEN FREQ HI
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
GEN FREQ LO
LMT
Min: 40
Max: 75
55 Hz
GEN FREQ LO
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Warning
SPD FREQ
MISMTCH
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Disabled
OVERCURRENT
LVL
Min: 5.0
Max: 30000.0
30 Amps/phase
OVERCURRENT
DLY
Min: 0.1
Max: 20.0
1.0 second
OVERCURRENT
ALM
Disabled
Warning
Visual Alarm
Audible Alarm
Soft Shutdown
Hard Shutdown
Soft Shutdown
REVERSE PWR Min: -50.0
Max: -1.0
-10.0 %
REV PWR DELAY Min: 0.1
Max: 20.0
5.0 seconds
MIN REVERSE
PWR
Min: -50.0
Max: -1.0
-5.0 %