Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 81
Generator High/Low Volt Limit Alarm
Even if the Alarm Set Points for the High/Low Limits are Disabled, the
Voltage Bias will
not allow adjustment beyond these limits.
The same is true for the synchronizer, which will not allow a gen breaker
closure if the High or Low Voltage limits are met or exceeded for a period of
time which exceeds the Gen Volt Timer Set Point. This is true even with
Voltage Matching disabled.
Voltage Alarm Delay
Sets minimum time, in seconds, allowed prior to activating either Generator
High/Low Voltage Limit Alarms. This allows for short period transient
over/under voltages to occur on the generator without setting off the
Generator Voltage Alarms.
Generator Frequency High Limit
Sets maximum allowable generator frequency level.
If frequency is above High Limit, generator is not considered stable, and is
unfit for breaker closure.
Generator Frequency Low Limit
Sets minimum allowable generator frequency level.
If frequency is below Low Limit, generator is not considered stable, and is
unfit for breaker closure.
Synchronous Speed (50/60 Hz)
Generator Low Frequency Limit (Speed Bias Cutout)
Operating
Range
Generator High Frequency Limit (Speed Bias Cutout)
Figure 4-21. Generator Over/Under Frequency
Generator High/Low Frequency Limit Alarm
Even if the Alarm Set Points for the High/Low Limits are Disabled, the
Speed Bias will not allow adjustment beyond these limits.
The same is true for the synchronizer, which will not allow a gen breaker
closure if the High or Low Frequency limits are met or exceeded.