Manual 26174 EGCP-2 Engine Generator Control Package
Woodward 1
Chapter 1.
General Information
Introduction
This manual describes how to Install and Operate the Woodward EGCP-2
Engine Generator Control Package, models 8406-120 and 8406-121.
Associated publications:
26175—Application Manual
26181—Communications Manual
26108—Security Levels Guide
03219—Product Specification
Regulatory Compliance
General Installation and Operation Notes and Warnings
The EGCP-2 is suitable for use in non-hazardous locations only.
Wiring must be in accordance with applicable electrical codes and in
accordance with the authority having jurisdiction.
Field wiring must be suitable for at least 90 °C.
Connect ground terminal to PE (Protective Earth).
More than one live circuit (see wiring diagram).
Control Electrical Ratings
Nominal supply voltage range 10–29 Vdc (12 or 24 volt systems)
Maximum power consumption
at rated voltage
20 W
Maximum PT input voltage range 150–300 Vac rms (8406-120)
Maximum PT input voltage range 50–150 Vac rms (8406-121)
Maximum CT current input range 0–6 A rms
Maximum generator frequency range 40–70 Hz
Technical Specifications
The relevant accuracies for this product are:
Element
A
ccuracy Description
Voltage Metering 1.0% at rated voltage At 23±5 °C
Current Metering 1.0% at 5 A ac At 23±5 °C
Power Metering 2.0% at rated V & I At 23±5 °C

Table of Contents