How do I fix a Woodward Controller that won't close to a dead bus?
- JJennifer HowardAug 29, 2025
If the unit won’t close to a dead bus, it could be due to: * A multiple unit system with the DEADBUS CLOSING set point in the configuration menu set to DISABLED. Enable the DEADBUS CLOSING set point in the configuration menu. * The synchronizer set point is set to CHECK. Set the synchronizer mode to the appropriate setting.