92 Freedom SW Owner’s Guide
Troubleshooting
F44 Battery Over
Temperature
Automatic Battery temperature is
over 140 °F (60 °C).
Poor battery
compartment
ventilation.
Stop charging if necessary.
Check cable connections.
Check battery voltage/current and
temperature. If battery is not accepting
charge, it may need to be replaced.
Check for excessive ambient
temperature and adequate ventilation
in the battery compartment.
Automatic BTS may be damaged. If the unit displays a temperature of
over 212 °F (100 °C), the BTS will
need to be replaced.
F46 Controller
Error
Manual Unit’s control board
may be damaged.
Service is required.
Table 3 Detected Fault Messages
Fault
Number Message Fault Type Cause Solution