97-0019-01-01 95
Troubleshooting
F57 FET1 Over
Temperature
Automatic Ambient temperature
may be too high.
Ensure adequate ventilation around the
Freedom SW.
Allow inverter to cool down and try
restarting.
Operating too large of
a load for too long
while inverting.
Remove excessive inverter loads.
Inverter cooling fan
may have failed.
If the temperature is above 104 °F
(40 °C), the fan should be on. Hold
your hand or a piece of paper to the
inverter vent to check if the fan is
working.
Both fans should be active at the same
time.
Inverter airflow intake
may be blocked.
Increase the clearance around the
inverter and/or unclog the airflow
intake vents.
F58 FET2 Over
Temperature
Automatic Same as F57. Same as F57.
Table 3 Detected Fault Messages
Fault
Number Message Fault Type Cause Solution
FSW Owners Guide.book Page 95 Tuesday, August 7, 2018 9:03 AM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex Freedom SW Series and is the answer not in the manual?

Xantrex Freedom SW Series Specifications

General IconGeneral
Output Voltage120 VAC
Output Frequency60 Hz
AC Transfer SwitchYes
Battery ChargerYes
Input Voltage12V, 24V, 48V DC
ProtectionsOver temperature, overload, short circuit

Related product manuals