Operating During Transition Between Grid Mode and Battery Mode
975-0799-01-01 73
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Transfer Mode
11 APL
APL(appliance)
UPS (UPS)
Selecting APL- appliance sets the transfer time from line to battery
to 20ms. Selecting UPS (uninterruptible power supply) sets the
transfer time from line to battery to 10ms. NOTE: Do not connect
motor loads when in UPS transfer mode. See Troubleshooting on
page 79.
Utility AC Under Voltage
Level
12 90 85 to 110
Inverter Shutdown
Recovery
13 MAT
At0(auto-
restart)
MAT(manual
restart)
The inverter shuts down when there is an over temperature,
overload, and short circuit condition. Selecting ATO (auto-restart)
will allow the inverter/charger to recover automatically from a
shutdown up to three times maximum. Selecting MAT (manual
restart) allows the user to restart the inverter/charger by performing
a manual reset, that is, by acknowledging the restart via the
display panel.
Audible Alarm
14 bON
bONAudible
BOF (Mute)
The alarm beeps once every five seconds.
Battery Type
20 FLD
FLDFlooded
AGM (AGM),
GELGel
USE (Custom)
LFP (LiFePO
4
The use of LFP (LiFePO
4
)as a battery type requires a compatible
BMS. See on page 13 for safety warning instructions.