Operating During Transition Between Grid Mode and Battery Mode
74 Freedom XC PRO Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Battery Temperature
21 HOt
CLD(Cold)
VRM(Warm)
HOT(Hot)
Selecting Cold from Warm will increase charger voltage by 0.4V.
Selecting Cold from Hot will increase charger voltage by 0.8V.
Custom Absorption
Voltage
22 14.6 12.0 to 18.0
The voltage setting value can be adjusted by 0.1 increments.
Available only when custom battery type is selected.
Custom Float Voltage
23 13.5 12.0 to 18.0
Charger Current
(Freedom XC PRO
2000)
24 100 5 to 100
The current setting value can be adjusted by 5A increments.
Charger Current
(Freedom XC PRO
3000)
24 150 5 to 150
Charger Ignition Control
26 OFF
OFF(OFF)
AT0 (Auto-ON)
See Description of Ignition Control Features on page 40.
Equalize Charging for
Flooded Battery
27 DIS
ENA (enable)
DIS (disable)
This setting is only available when Flooded battery type is
selected. It allows only one hour of equalize charging once.