Wiring the Inverter/Charger
975-0209-01-01 2–15
Disconnecting
battery cables
To disconnect the batteries for service:
1. Turn the Inverter
ON/OFF switch OFF.
2. Disconnect all AC inputs.
3. Disconnect the battery cables.
CAUTION: Equipment damage
Never disconnect the battery cables while the inverter is delivering power or the battery
charger is operating. Disconnecting the battery cables could cause a rapid voltage increase
that could damage the charger or other DC loads. Keep in mind that the Inverter
ON/OFF
switch on the inverter/charger does not turn off the charger section; it only turns off the
inverter.