Versant 80 Press 
Customer Expectation & Installation Guide   
Determining the Amp/Circuit Requirements 
Use the following formula to determine/calculate the amperage/circuit requirements for all devices associated with the press; this 
includes the Print Server, OHCF, and optional finishing devices. 
NOTE:  This formula does not calculate the press since it is on its own dedicated circuit. 
1. 
Determine the amps required for each device. 
2. 
Calculate the total amp sum of all the devices. 
3. 
The sum total is: 
• 
12 or below; therefore, a 15 amp circuit may be used with NEMA 5-15R. However, a 20 amp circuit is recommended using 
NEMA 5-20R receptacles. 
• 
12.1 - 16; a 20 amp circuit is required (NEMA 5-20R receptacles). 
4. 
Calculate the total number of devices associated with press, including the Print Server, OHCF, and all optional finishing 
devices. 
This calculation is number of receptacles required. Refer to the following two examples. 
Recommended Wall Receptacle Placement 
The recommended wall receptacle placement for the print server, OHCF, the press, and its accessories are shown in the following illustration. 
This is for USA receptacles only. It is recommended that receptacles be grouped as shown in relation to the print engine. 
The following illustration shows a full configuration consisting of a standalone print server, Advanced HCF, the press, Interface Module, GBC 
AdvancedPunch Pro, High Capacity Stacker, Booklet Maker Finisher with C/Z Folder, and SquareFold Trimmer Module. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Electrical Installation Considerations 
Press Electrical Considerations 
  Ground Fault Protection is provided which meets Xerox internal safety requirements and exceeds the Industry Standards for 
Information Technology Equipment. 
  The electrical outlet must be located within 6 feet (1.83 m) to the right of the right rear corner of the main processor, or no 
more than 3 feet (0.914 m) to the left of the left rear corner of the main processor (when facing the equipment) 
  The power cord must have sole use of the circuit. The outlet/circuit cannot be shared with any other devices or equipment 
  OHCF should be placed within 6 feet (1.83 meters) of wall outlets. 
  OHCF have their own power cord and must be plugged into an outlet separate from the print engine. Ensure that there are 
enough wall outlets.