EasyManuals Logo

Xinje XC Series User Manual

Xinje XC Series
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
5 Input Specifications and Wiring Methods
5-3-4AB Phase Counter's Frequency Multiplication Setting
To AB phase counter, user can modify the value in FLASH data registers FD8241, FD8242,
FD8243 to set the frequency multiplication value. When the value is one, it is one time frequency;
when the value is four, it is 4 times frequency.
1For more information about high speed counter, please refer to XC series PLC instruction manual
2To some special model, only one axis can be set as one time frequency or 4 times frequency, the left two axes
are separately one time frequency and 4 times frequency.
Register
Function
Setting Value
Content
FD8241
Frequency Multiplication of C630
1
1 time frequency
4
4 time frequency
FD8242
Frequency Multiplication of C632
1
1 time frequency
4
4 time frequency
FD8243
Frequency Multiplication of C634
1
1 time frequency
4
4 time frequency