8 expansion devices
Items
Analogue Input (AD)
Voltage Input
Current Input
Analogue Input Range
DC05V, 010V
DC020mA, 420mA
Max Input Range
DC±18V
DC040mA
Analogue Output
Range
-
Digital Input Range
-
Digital Output Range
14 bits binary (016383)
Distinguish Ratio
1/16383(14Bit); the convert data is stored in PLC in form of Hex. (14Bit)
(14Bit)
PID Output Value
0K4095
Integral precision
0.8%
Convert Speed
20ms/CH
Power Supply
DC24V±10%, 100mA
0V
24V
C1
C0
AI0 VI1 C2 AI2 VI3
AI3C3VI2A11VI0
CH
NAME
SIGNAL
CH
NAME
SIGNAL
CH0
AI0
Current analogue input
CH1
AI1
Current analogue input
VI0
Voltage analogue input
VI1
Voltage analogue input
C0
COM of CH0
C1
COM of CH1
CH2
AI2
Current analogue input
CH3
AI3
Current analogue input
VI2
Voltage analogue input
VI3
Voltage analogue input
C2
COM of CH2
C3
COM of CH3
-
24V
+24V power supply
0V
COM of power supply
Specification
2
Terminal Arrangement
3
4CH analogue input: voltage and current input selectable; Voltage input range is 05V, 0
10V selectable, current input range is 020mA420mA selectable;
14 bits high precision analogue input;
As the special module, 7pcs XC-E4AD can be connected to one XC series PLC main unit;
XC-E4AD module support PID auto tune function;

Table of Contents

Other manuals for Xinje XC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje XC Series and is the answer not in the manual?

Xinje XC Series Specifications

General IconGeneral
BrandXinje
ModelXC Series
CategoryController
LanguageEnglish

Related product manuals