EasyManua.ls Logo

Xinje XC Series - Page 91

Xinje XC Series
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 expansion devices
the data exchange quantity, expand the data memory space;
Items
Analogue Input (AD)
Temp. inputPT
Analogue output (DA)
Analogue Input
Current
0
20mA
4
20mA
PT100
-
Voltage
05V
010V
Temperature Range
-
-100~327
-
Max input range
DC040mA
-
-
Analogue output
range
-
-
Current
010V
05V
Voltage
020mA
420mA
Digital input range
-
-
10 bits binary (0~1023)
Digital Output range
16 bits binary (0~65535)
-1000~3500
-
Distinguish Ratio
1/16383(16Bit)
0.01
1/1023(10Bit)
PID Output value
0~K4095
-
Integral precision
0.8%
±0.01
0.8%
Convert speed
20ms/CH
3ms/CH
Power supply
DC24V±10%, 100mA
PT0
COM AI0 VI1 CI1
AI1CI0VI0PT1COM
VA
VB
24V
0V
VO0 VO1 CO1
IO0 CO0 IO1
Name
Terminals
Comments
Input terminals
PT0, PT1
Temperature
Input
Analogue input, PT100 temperature sensor
(-100350)
VI0, VI1
Analogue Input
Voltage
Input
0~10V or 0~5V
Specification
2
Terminal Arrangement
3

Table of Contents