Xtreme Power Conversion Corporaon
P91, TX91, TX91L, TXVR Service Manual
Page 4
Uninterrupble Power Supply
2. Specicaons
MODEL NUMBER
P91-5K P91-6K P91-10K
CAPACITY Power rang 5kVA (5kW) 6kVA (6kW) 10kVA (10kW)
INPUT
Voltage 110–300VAC*
Frequency 50/60Hz
OUTPUT
Voltage 200/208/220/230/240VAC (208/120V or 240/120V with oponal transformer)
Frequency 50/60Hz ± 4Hz
THD (full load) < 4%
Overload capacity 110% 10 min; 130% 1 min; > 130% 1 sec
Eciency Up to 95% online mode or 99% ECO mode
BATTERY
Charger amps 1–4A
Nominal/oat voltage 240/273VDC
DIMENSIONS &
Dimensions (W x D x H) 17.2 x 23.6 x 3.5 in
WEIGHT
Weight 33.1 lbs 39.7 lbs
BYPASS
Model XBDM-P91A XBDM-P91B
DISTRIBUTION
Input connecon L6–30P (5, 6kVA) Terminal Block (5,6,10kVA)
MODULE Output connecon
(2) L6-30R+(2) C19 Terminal block + (1) L6-30R+(2) C19
Oponal: L6–30R, L6–20R, 6–20R Oponal: L6–30R, L6–20R, 6–20R
ENVIRONMENT
Operang temperature 32–104°F (0–40°C)
Audible noise < 55dBA < 58dBA
Altude 11,500  above sea level
APPROVALS UL, FCC, RoHS (pending)
WARRANTY 3 years electronics, 3 years baery warranty (USA and Canada)
COMMUNICATIONS INTERFACE RS-232, USB, EPO, intelligent slot for oponal cards (Web/SNMP, Relay/dry contact, Modbus)
INCLUDED IN BOX Soware CD, horizontal brackets, tower pedestals, USB cable
AVAILABLE OPTIONS 5 year extended warranty, 4-post rail kit, 2-post shelf kit, transformer
*Depending on load level.
MODEL NUMBER
TXVR-3.8K TXVR-5K TXVR-6K TXVR-10K
CAPACITY
Power rang
3.8kVA/3.8kW 5kVA/5kW 6kVA/6kW 10kVA/10kW
INPUT
Voltage (nominal)
208/220/230/240VAC
Voltage range
110-300VAC
Frequency
4654Hz or 5664Hz
OUTPUT
Voltage
240/120VAC or 230/115VAC
Voltage Regulaon ± 1%
Frequency 50Hz ± 0.1Hz or 60 Hz ± 0.1Hz
Overload capacity 200% for 1 min 150% for 1 min 130% for 1 min
Eciency up to 97% ECO mode, 91% online mode
Harmonic Distoron
<2% @ 100% linear load (regardless of input distoron)
PHYSICAL
Input/output
Terminal blocks or oponal PDU
Dimensions (W x D x H) 9.8 x 23.2 x 32.4 in
Weight
142 lbs 145 lbs 148 lbs 187 lbs
OPTIONAL PDU
Input connecon
Terminal Block with 6 L6-30P* Terminal Block
120V receptacle opons 5-15/20R
240V receptacle opons
L6-30R, L6-20R, 6-15/20R, C19
ENVIRONMENT
Temperature
32–104°F (0–40°C)
Audible noise < 50dBA
Altude 11,500  above sea level
APPROVALS UL, cUL, RoHS
WARRANTY 3 years electronics (USA and Canada)
COMMUNICATIONS INTERFACE RS-232, EPO, intelligent slot for oponal cards (Web/SNMP, Relay/dry contact, Modbus)
INCLUDED IN BOX
User manual, RS-232 communicaon cable, ViewPower Soware CD
AVAILABLE OPTIONS 5 year extended warranty, output PDU, input L6-30P cord (for 3.8kVA, 5kVA, 6kVA)