9 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual 47
Note: This is a paired assembly (124/134).
Table 11 Reply Mapping - 134
Current Status Dynamic Assy (Vendor Specific Yaskawa Electric (YE) Assy) - 135
(0x87)
Output Frequency
Actual Drive Speed
Monitors drive output frequency
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Byte
Write
Success
Read Success Write Failure Read Failure Busy
Illegal
Function
Code
Function Code
Equals Zero
1 0x90 0x8E 0x94 0x94 0x8E/0x90 0x94 0
2 Class Number Class Number 0 0 Class Number 0 0
3
Attribute
Number
Attribute
Number
00
Attribute
Number
00
4 0 Data Low Byte
DeviceNet Error
Code
DeviceNet Error
Code
0 0x08 0
5 0 Data High Byte 0xFF 0xFF 0 0xFF 0
Input
Instance
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
135
0 FAULT ALARM READY
Speed
Agree
Reset
REV
Running
ZSP Running
1 Service Code
2Class
3 Attribute
4 Data (Low Byte)
5 Data (High Byte)
6 Actual Current (Low Byte)
7 Actual Current (High Byte)
Parameter Data
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: No Reset
1: Reset
Speed Agree
Speed Agree
0: No Speed Agree
1: Actual speed at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
Parameter Data

Other manuals for YASKAWA 1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA 1000 Series and is the answer not in the manual?

YASKAWA 1000 Series Specifications

General IconGeneral
Series1000 Series
CategoryDC Drives
Cooling MethodForced air cooling
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short Circuit
Communication InterfaceModbus RTU
Storage Temperature-20°C to +60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Input Voltage200-240V AC, 380-480V AC