Programming 59
The Drive has the capability to control 2 motors independently. A second motor may be selected using a multi-function
contact input (H1-0x = 16). This parameter select the control method for motor 2. The control method for motor 1 is selected
via parameter A1-02.
Fig. 39 Two Motor Switching Set-up
The following is a list of parameters that become effective when motor 2 is selected.
E3-08E
E3-02 Motor 2 Maximum Output Frequency
Setting Range: 0.0 to 400.0 Hz
Factory Default: 60.0 Hz
E3-03 Motor 2 Maximum Output Voltage
Setting Range: 0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)
Factory Defaults: 230.0V (240V Models)
480.0V (480V Models)
E3-04 Motor 2 Base Frequency
Setting Range: 0.0 to 400.0 Hz
Factory Default: 60.0 Hz
Table 12 Motor 2 Parameters
V/f Pattern 2 Motor Setup 2
E3-01 Control Method 2 E4-01 Motor Rated FLA
E3-02 Max Frequency E4-02 Motor Rated Slip
E3-03 Max Voltage E4-03 No-Load Current
E3-04 Base Frequency E4-04 Number of Motor Poles
E3-05 Mid Frequency E4-05 Terminal Resistance
E3-06 Mid Voltage E4-06 Leakage Inductance
E3-07 Min Frequency E4-07 Motor Rated Power
E3-08 Min Voltage - -
G5
M
M
Motor 1
Motor 2