YASKAWA TM.iQp.02 iQpump Drive Programming Manual 115
For example, if the iQpump drive needs to display the Elapsed Timer as the Power-On monitor, then o1-01 must be set to “13” and o1-02
must be set to “4”. The next time iQpump drive power is cycled, the digital operator displays U1-13 (Elapsed Time), U1-14 (Flash ID),
and U1-15 (Term AI Level).
o1-05 LCD Contrast Adjustment
Setting Range: 1, 3 or 5
Factory Default: 3
The contrast setting of the LCD display of the digital operator can be adjusted by the setting of parameter o1-05. The higher the number
programmed into o1-05, the darker the background will become. Set o1-05 to the value that makes the LCD the easiest to view at the
normal viewing distance and angle.
o1-06 User Monitor Selection Mode
o1-07 Second Line User Monitor
Setting Range: 1 to 94
Factory Default: 2
o1-08 Third Line User Monitor
Setting Range: 1 to 94
Factory Default: 91
Normally the monitors shown directly below the active monitor are the next two sequential monitors. If o1-06 (User Monitor Selection
Mode) is set to “1: 3 Mon Selectable,” those two monitors are locked as specified by parameters o1-07 and o1-08 and will not change as
the top parameter is scrolled with the INCREASE and DECREASE keys.
Setting Description
0 3 Mon Sequential
1 3 Mon Selectable (factory default)
Output Frequency
Output Current
-DRIVE- Rdy
Frequency Ref
U1-01= 60.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-02= 60.00Hz
U1-03= 10.05A
A
ctive Monitor
Next two
sequential
monitors
A
ctive Monitor Title
-DRIVE- Rdy
Elapsed Time
U1-13= 2H
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-14= 03010
U1-16= 51.2%
A
ctive Monitor
A
ctive Monitor Title
Next two
sequential
monitors
Flash ID
Term A I L e v e l
15
-DRIVE- Rdy
PI Feedback
U1-24= 64.55%
- - - - - - - - - - - - - - - - - - - - - - - - - - - - -
U1-37= 0.00%
U1-38= 2.50%
A
ctive Monitor
o1-07
o1-08
A
ctive Monitor Title
PI Output
PI Setpoint
o1-07=37
o1-08=38