114 YASKAWA TM.iQp.02 iQpump Drive Programming Manual
o1 Monitor Configuration
o1-01 User Monitor Selection
Setting Range: 6 to 94
Factory Default: 6
o1-02 Power-On Monitor
When the iQpump drive is powered up, three monitors are displayed on the digital operator. The first and largest monitor is the “Power-
On” monitor. The factory default “Power-On monitor” is Speed Command (U1-01). Below the Speed Command monitor are the next
two sequential monitors, Output Frequency (U1-02) and Output Current (U1-03). Pressing the INCREASE key once scrolls the monitors
to show the User Monitor as selected by o1-01. The factory default for o1-01 is the Output Voltage monitor (U1-06).
The active monitor displayed when the iQpump drive is powered on can be changed to either be U1-01 (Speed Command), U1-02
(Output Frequency), U1-03 (Output Current), or the User Monitor. Whichever monitor is selected as the Power-On top monitor, the two
monitors displayed below it are the next two sequential monitors. See example below.
Setting Description
6 Output Voltage (factory default)
7 DC Bus Voltage
8Output Power
10 Input Terminal Status
11 Output Terminal Status
12 Drive Operation Status
13 Cumulative Operation Time
14 Software Number
15 Terminal A1 Input Voltage
16 Terminal A2 Input Voltage
18 Motor Secondary Current (Iq)
20 Output Frequency After Soft Start
24 PI Feedback Value
28 CPU Number
34 First Parameter Causing an OPE
36 PI Input
37 PI Output
38 PI Setpoint
39 Memobus Communication Error Code
40 Heatsink Cooling Fan Operation Time
51 Auto Mode Frequency Reference Value
52 Hand Mode Frequency Reference Value
53 PI Feedback 2 Value
90 Pump Setpoint
91 Pump Feedback
92 Pump Status
93 Total Setpoint Compensation
94 Motor Speed
<0032>
Setting Description
1 Auto: Setpoint Reference (factory default)
2 Output Frequency
3Output Current
4 User Monitor (set by o1-01)

Table of Contents