o2-10 Cumulative Cooling Fan Operation Time Setting
Setting Range: 0 to 65535 Hours
Factory Default: 0 Hours
The elapsed time of heatsink cooling fan operation is tracked by the U1-40 monitor. Much like the o2-07 parameter can be used to adjust
or reset the iQpump drive operation elapsed timer, parameter o2-10 can be used to adjust the time displayed by the U1-40 monitor in the
event of fan replacement.
o2-12 Fault Trace / Fault History Clear Function
The operator can clear the Fault Trace (U2) and Fault History logs by setting o2-12 = “1: Enabled”. Clearing the Fault Trace and Fault
History logs erases all the information.
o2-14 kWh User Monitor Initialization
The kWh monitors (U1-29 and U1-30) track the power usage of the iQpump drive and are not reset by powering down the Drive. To reset
the monitors back to zero, set o2-14 = “1: Clear all”.
Setting Description
0 Disabled (No Effect) (factory default)
1Enabled
Setting Description
0 Disabled (No Change) (factory default)
1Clear All
-DRIVE-
FAN Elapsed Time
U1-40 = 152H