128 YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Figure 1. 98
Figure 103 Loss of Prime (LOP)
P1-15 Low Water Input
The iQpump drive can be configured to detect a low water level condition. To activate the low water level detection requires one of the
multi-function digital inputs to be programmed for low water level (H1-xx = 85). The multi-function digital input can be configured to
accept a normally closed or normally open contact by programming the Low Water Input (P1-15).
This function is only active during operation in the Auto Mode.
Important: Refer to H1-xx = 85 on page 158 for further description of the low water level function.
Setting Description
0 Closed at Low Water (factory default)
1Open at Low Water
TIME
Loss of Prime
(LOP) Fault
Loss of Prime
P1-12
P1-14
Fmax
- 1 Hz
OUTPUT
CURRENT
OUTPUT
FREQUENCY