YASKAWA TM.iQp.02 iQpump Drive Programming Manual 199
U1-16 004FH
Terminal A2 Input Voltage
Ter m A2 le ve l
Displays the input current (or voltage) on Terminal A2, as a percentage of 20 mA (or 10 Vdc).
U1-18 0051H
Motor Secondary Current (Iq)
Mot SEC Current
Displays the amount of current being used by the motor to produce torque (Iq).
U1-20 0053H
Output Frequency After Soft
Start
SFS Output
Displays the frequency reference (speed command) after the accel and decel ramps.
U1-24 0057H
PI Feedback Value
PI Feedback
Displays the feedback signal when PI control is used.
U1-28 005BH
CPU Number
CPU ID
Displays control board hardware revision.
U1-29 005CH
kWh
kWh Lo 4 Digits
Displays the accumulated kWh.
U1-30 005DH
MWh
kWh Hi 5 Digits
Displays the accumulated MWh.
U1-34 0061H
First Parameter Causing an OPE
OPE Detected
Displays the parameter number causing an “OPE” fault.
U1-36 0063H
PI Input
PI Input
Displays the “error” in the PI regulator. (U1-36 = PI Setpoint - PI Feedback).
U1-37 0064H
PI Output
PI Output
Displays the output of the PI as a percentage of maximum frequency (E1-04).
U1-38 0065H
PI Setpoint
PI Setpoint
Displays the setpoint of the PI regulator (U1-38 = PI reference + PI bias).
U1-39 0066H
Memobus Communication Error
Code
Transmit Err
U1-40 0067H
Heatsink Cooling Fan Operation
Time
FAN Elapsed Time
Displays total operating time of the heatsink cooling fan.
U1-90 0720H
Pump Setpoint
Pump Setpoint
Displays drive setpoint.
Resolution 0.1
Note: Does not include setpoint compensation (U1-93).
U1-91 0721H
Pump Feedback
Pump Feedback
Displays scaled feedback.
Resolution 0.1
U1-92 0722H
Pump Status
Pump Status
Display pump running status.
Parameter No.
Modbus
Address
Parameter Name Digital
Operator Display
Description
Monitor
1: CRC error
1: Data length error
Not used. Always 0.
1: Parity error
1: Overrun error
1: Framing error
1: Timeover
Not used. Always 0.
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0
1: Drive (Pump 1)
1: Pump 2 on
1: Pump 3 on
Not used. Always 0.