EasyManua.ls Logo

YASKAWA iQpump Series

YASKAWA iQpump Series
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YASKAWA TM.iQp.02 iQpump Drive Programming Manual 207
Table 36 480 VAC Drives
Drive Model
CIMR-P7U-
-107
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
C6-02
<0032>
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
40P4 0.5/0.75 576.40 15 kHz 1.0 0.6 38.198 0.1 0.1 0.3 95×C 5
40P7 1 447.40 15 kHz 1.6 0.8 22.459 0.1 0.2 0.3 95×C 7.5
41P5 1.5/2 338.80 15 kHz 3.1 1.4 10.100 0.2 0.3 0.3 95×C 10
42P2 3 313.60 15 kHz 4.2 1.5 6.495 0.3 0.4 0.3 90 ×C 10
43P7 5 245.80 15 kHz 7.0 2.3 3.333 0.5 0.5 0.3 95×C 12
45P5 7.5 189.50 15 kHz 13.3 2.6 1.595 1.0 0.6 0.3 95×C 10
47P5 10 145.38 15 kHz 19.9 4.0 1.152 1.0 0.7 0.3 90×C 20
49P0 15 145.46 15 kHz 21.0 4.4 0.922 1.0 0.8 0.3 95°C 23
4011 15/20 140.88 8 kHz 26.5 5.6 0.922 2.0 0.8 0.3 95×C 23
4015 25 126.26 10 kHz 32.9 7.6 0.550 2.0 0.9 0.3 95×C 17
4018 30 115.74 10 kHz 52.3 7.8 0.403 2.0 1.0 0.6 98×C 17
4024 40 89.08 10 kHz 52.0 8.6 0.269 2.0 1.1 0.6 85°C 20
4030 40/50 92.54 8 kHz 65.6 10.9 0.269 2.0 1.1 0.6 85×C 20
4037 60 76.32 8 kHz 79.7 19.1 0.155 2.0 1.1 0.6 85×C 20
4045 75 71.56 8 kHz 95.0 22.0 0.122 2.0 1.2 0.6 90×C 20
4055 100 67.20 5 kHz 130.0 24.0 0.088 2.0 1.2 1.0 90×C 20
4075 125 46.20 5 kHz 130.0 36.0 0.092 2.0 1.3 1.0 98×C 16
4090 150 38.91 8 kHz 156.0 40.0 0.056 2.0 1.5 1.0 108×C 16
4110 200 36.23 5 kHz 190.0 49.0 0.046 2.0 1.7 1.0 100×C 16
4160 250 30.13 5 kHz 270.0 70.0 0.029 2.0 1.8 1.0 108×C 14
4185 300/350 30.57 2 kHz 310.0 81.0 0.025 2.0 0.7 1.0 95×C 15
4220 400/450 27.13 2 kHz 370.0 96.0 0.020 2.0 0.8 1.0 100×C 15
4300 500+ 21.76 2 kHz 500.0 130.0 0.014 2.1 0.9 1.0 95×C 15
Note: b8-04 = Energy Savings Coefficient
C6-02 = Carrier Frequency
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level