YASKAWA TM.iQp.02 iQpump Drive Programming Manual 207
Table 36 480 VAC Drives
Drive Model
CIMR-P7U-
-107
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
C6-02
<0032>
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
40P4 0.5/0.75 576.40 15 kHz 1.0 0.6 38.198 0.1 0.1 0.3 95×C 5
40P7 1 447.40 15 kHz 1.6 0.8 22.459 0.1 0.2 0.3 95×C 7.5
41P5 1.5/2 338.80 15 kHz 3.1 1.4 10.100 0.2 0.3 0.3 95×C 10
42P2 3 313.60 15 kHz 4.2 1.5 6.495 0.3 0.4 0.3 90 ×C 10
43P7 5 245.80 15 kHz 7.0 2.3 3.333 0.5 0.5 0.3 95×C 12
45P5 7.5 189.50 15 kHz 13.3 2.6 1.595 1.0 0.6 0.3 95×C 10
47P5 10 145.38 15 kHz 19.9 4.0 1.152 1.0 0.7 0.3 90×C 20
49P0 15 145.46 15 kHz 21.0 4.4 0.922 1.0 0.8 0.3 95°C 23
4011 15/20 140.88 8 kHz 26.5 5.6 0.922 2.0 0.8 0.3 95×C 23
4015 25 126.26 10 kHz 32.9 7.6 0.550 2.0 0.9 0.3 95×C 17
4018 30 115.74 10 kHz 52.3 7.8 0.403 2.0 1.0 0.6 98×C 17
4024 40 89.08 10 kHz 52.0 8.6 0.269 2.0 1.1 0.6 85°C 20
4030 40/50 92.54 8 kHz 65.6 10.9 0.269 2.0 1.1 0.6 85×C 20
4037 60 76.32 8 kHz 79.7 19.1 0.155 2.0 1.1 0.6 85×C 20
4045 75 71.56 8 kHz 95.0 22.0 0.122 2.0 1.2 0.6 90×C 20
4055 100 67.20 5 kHz 130.0 24.0 0.088 2.0 1.2 1.0 90×C 20
4075 125 46.20 5 kHz 130.0 36.0 0.092 2.0 1.3 1.0 98×C 16
4090 150 38.91 8 kHz 156.0 40.0 0.056 2.0 1.5 1.0 108×C 16
4110 200 36.23 5 kHz 190.0 49.0 0.046 2.0 1.7 1.0 100×C 16
4160 250 30.13 5 kHz 270.0 70.0 0.029 2.0 1.8 1.0 108×C 14
4185 300/350 30.57 2 kHz 310.0 81.0 0.025 2.0 0.7 1.0 95×C 15
4220 400/450 27.13 2 kHz 370.0 96.0 0.020 2.0 0.8 1.0 100×C 15
4300 500+ 21.76 2 kHz 500.0 130.0 0.014 2.1 0.9 1.0 95×C 15
Note: b8-04 = Energy Savings Coefficient
C6-02 = Carrier Frequency
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level