YASKAWA TM.iQp.02 iQpump Drive Programming Manual 41
Table 4 Preset V/f Patterns
If one of the custom V/f patterns is selected, then parameters E1-04 through E1-13 will determine the V/f pattern.
Table 4 is for 240 V class units only. For 480 V class units multiply the voltage value by 2.
Important: When a factory Initialization is performed, the setting of E1-03 is unaffected but the settings of E1-04 through E1-13 are
returned to their factory default settings.
E1-04 Maximum Output Frequency
Setting Range: 0.0 to 120.0 Hz
Factory Default: 60.0 Hz
E1-05 Maximum Output Voltage
Setting Ranges: 0.0 to 255.0 V (240 V Models)
0.0 to 510.0 V (480 V Models)
Factory Defaults: 240.0 V (240 V Models)
480.0 V (480 V Models)
Specifications E1-03 V/f Pattern *1 Specifications E1-03 V/f Pattern *1
General-
purpose
50 Hz 0
High
Starting
Torque *2
50 Hz
High Starting
Torque 1
8
High Starting
Torque 2
9
60 Hz Saturation
1
F
60 Hz
High Starting
Torque 1
A
50 Hz Saturation 2
High Starting
Torque 2
B
72 Hz 3
High Speed
Operation
90 Hz C
Va ri a bl e
Torque
50 Hz
Var ia bl e
Torque 1
4
120 Hz D
Var ia bl e
Torque 2
5
60 Hz
Var ia bl e
Torque 1
6
Var ia bl e
Torque 2
7
(Hz)
(V)
230
17
10
01.32.5 50
0
230
(V)
28
22
15
13
(Hz)
01.32.5 50
9
8
(Hz)
01.53.0 50 60
17
10
2
1
F
(V)
230
230
(V)
28
22
17
13
(Hz)
01.53.0
B
A
60
(Hz)
01.53.0 60 72
17
10
3
(V)
230
(Hz)
01.53.0 60 90
17
10
C
(V)
230
230
(V)
57
40
10
9
(Hz)
0 1.3 25 50
5
4
(Hz)
0 1.5 3.0 60 120
17
10
D
(V)
230
230
(V)
57
40
10
9
(Hz)
01.5 30 60
7
6

Table of Contents

Related product manuals