64 YASKAWA TM.iQp.02 iQpump Drive Programming Manual
Function: Fref/Set Agree 1 (Setting: 3)
The “Fref/Set Agree 1” output will close whenever the actual output frequency and the Speed Command are within the Speed Agree
Width (L4-02) of the programmed Speed Agree Level (L4-01).
Figure 1. 52
Figure 52 Fref/Set Agree 1 Timing Diagram
Function: Freq Detect 1 (Setting: 4)
A “Freq Detect 1” output will be closed whenever the output frequency is equal to or below the value of the programmed Speed Agree
Level (L4-01). The Speed Agree Width (L4-02) is the hysteresis to the Freq Detect 1 function. Whenever the output frequency
approaches the Speed Agree Level while accelerating it will need to be equal to or exceed the Speed Agree Level (L4-01) plus the Speed
Agree Width (L4-02) before the Freq Detect 1 output will energize.
As the output frequency approaches the Speed Agree Level while decelerating, the Freq Detect 1 output will de-energize exactly at the
Speed Agree Level.
The Freq Detect 1 function is effective during both forward and reverse operation.
Figure 1. 53
Figure 53 Freq Detect 1 Timing Diagram
Frequency Agree
Signal
Output Frequency
t
a
Frequency
Reference
a
D t ti Width (L4 02) X 2
Speed Agree Level
(L4-01)
t
t
Speed Command
Frequency/Set Agree 1
Signal
a - Speed Agree Width (L4-02) X2
ON (CLOSED)
OFF (OPEN)
TIME
Frequency
Detection Signal
Output
Frequency
t
a
a
- Detection Width (L4-02)
L4-01
Detection 1 Signal
ON (CLOSED)
OFF (OPEN)
a - Speed Agree Width (L4-02)
a
t
TIME