■ Terminal Signal Level Selections
When the iQpump drive is equipped with the optional, removable terminal board with 4-20 mA outputs (p/n ETC618120), parameters
H4-07 and H4-08 determine whether analog outputs are configured as 0-10 Vdc or 4-20 mA. Refer to the documentation for the optional
terminal board as the proper jumper settings are required in addition to programming H4-07 and H4-08.
If the standard removable terminal board is being used, the settings of H4-07 and H4-08 have no effect.
Parameter No. Setting Description
H4-07 0 Terminal FM Signal Level Selection, 0 - 10 Vdc (factory default)
H4-08 1 Terminal AM Signal Level Selection, 4 - 20 mA