YASKAWA TM.iQp.02 iQpump Drive Programming Manual 97
Figure 1.82
Figure 87 Motor Overload Protection Time based on Output frequency and Load
L1-03 Motor Overheat Alarm Operation Selection
L1-04 Motor Overheat Fault Operation Selection
L1-05 Motor Temperature Input Filter Time
Setting Range: 0.00 to 10.00 sec
Factory Default: 0.20 sec
The iQpump drive can be programmed to accept a PTC (Positive Temperature Coefficient) Thermistor input for monitoring motor
temperature. By setting parameter H3-09 = “E: Motor Temperature,” and attaching the PTC thermistor per the figure below, the iQpump
drive can react to the increasing motor winding temperature with both an alarm (L1-03) and a fault (L1-04).
Setting Description
0 Ramp to Stop
1 Coast to Stop
2Fast-Stop
3 Alarm Only (
factory default)
Setting Description
0 Ramp to Stop
1 Coast to Stop (
factory default)
2Fast-Stop
125%
4
2
Time
(Minutes)
Output Current
(Percent of motor FLA)
E2-01 200%
6
8
10
60Hz
10Hz
175%
150%