3 Electrical Installation
YASKAWA Europe TOEP C710616 92D AC Drive L1000H Quick Start Guide EN 15
Control Circuit Terminal Functions
NOTICE: The terminals HC, H1, H2 are used for the Safe Disable function. Safe Disable can be used to enable/disable the drive. If
special requirement are fulfilled, it can also be utilized for reducing the number of motor contactors to one. Refer to Safe Disable Input
Function on page 42 for details. Always remove the wire link between HC, H1, or H2 when using Safe Disable.
NOTICE: The wiring length to terminals HC, H1 and H2 should not exceed 30 m.
NOTICE: When connecting a reactive load such as a relay coil to a photo coupler output, attach a flywheel diode to the load (relay coil)
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Digital Inputs
S1
Multi-function Up Command (Closed: Up, Open:
Stop)
Photocoupler
24 Vdc, 8 mA
Use the wire link between terminals SC and SN or between SC and
SP to select sinking or sourcing, and to select the power supply.
S2
Multi-function Down Command (Closed: Down,
Open: Stop)
S3
Multi-function input 3 (Not used)
S4
Multi-function input 4 (Nominal Speed)
S5
Multi-function input 5 (Intermediate Speed)
S6
Multi-function input 6 (Inspection Speed)
S7
Multi-function input 7 (Not used)
S8
Multi-function input 8 (Not used)
Digital Input
Power Supply
SC
Multi-function input common
Photocoupler, 24 Vdc, 8 mA
Use the wire link between terminals SC and SN or between SC and
SP to select sinking or sourcing, and to select the power supply.
SN 0 V
SP +24 Vdc
Safe Disable
Inputs
H1
Safe Disable input 1
24 Vdc, 8 mA
One or both open: Drive output disabled
Both closed: Normal operation
Internal impedance: 3.3 k
Off time of at least 1 ms
Set the S3 jumper to select sinking or sourcing, and to select the
power supply.
H2
Safe Disable input 2
HC
Safe Disable function common Common for the Safe Disable function
Analog Inputs
+V
Power supply for analog inputs 10.5 Vdc (max. allowable current 20 mA)
–V
Power supply for analog inputs -10.5 Vdc (max. allowable current 20 mA)
A1
Multi-function analog input 1 (Oil Temperature) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
A2
Multi-function analog input 2 (Not used) -10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 k)
AC
Analog Input common 0 V
E (G)
Ground for shielded lines and option cards –
Fault Relay
MA
N.O. output
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
MB
N.C. output
MC
Fault output common
Multi-Function
Relay Output
M1
Relay output 1 (Safe Disable Status)
M2
M3
Relay output 2 (Not used)
M4
M5
Relay output 3 (Not used)
M6
Multi-Function
Photocoupler
Output
P1
Photocoupler output 1 (Safe Disable Status)
Photocoupler output 48 Vdc, 2 to 50 mA
C1
P2
Photocoupler output 2 (Speed Agree)
C2
Monitor Output
FM
Analog monitor output 1 (Output speed)
-10 to +10 Vdc, 0 to +10 Vdc
AM
Analog monitor output 2 (Output current)
AC
Monitor common 0 V
Safety Monitor
Output
DM+
Safety monitor output
Outputs status of Safe Disable function. Refer to Safe Disable
Monitor Output Function and Digital Operator Display on
page 44 for details..
DM–
Safety monitor output common